Single package heat pumps

Energy Efficiency Regulations

Regulatory definition

Single package central heat pump, a single-phase or three-phase air-to-air central heat pump that is a centrally ducted single package unit and has a cooling or heating capacity of less than 19 kW (65,000 Btu/h). It does not include a single package vertical heat pump.

Compliance date

Manufactured on or after January 1, 2025, for single package central heat pumps (single-phase)

Manufactured on or after January 1, 2026, for single package central heat pumps (three-phase)

For models manufactured prior, refer to the Regulations

Compliant product models

Single package heat pumps, single-phase as listed on NRCan’s searchable database

Single package heat pumps, three-phase as listed on NRCan’s searchable database

Testing standard

10 C.F.R. Appendix M1 for single-phase models

10 C.F.R. Appendix F1, except that the very low temperature heating test (H4) must be conducted.

Energy efficiency regulations by province

Some provinces also have their own energy efficiency regulations for many of the federally regulated products – find out which ones!

Energy efficiency standard

Energy performance standard for single package central air conditioners and single package central heat pumps under 19 kW (65,000 Btu/h)

Single Phase

Energy-using product

Energy performance standard

Single package central heat pumps, other than those that are space-constrained

SEER 2 ≥ 13.4

HSPF 2 (Region V) ≥ 5.4

Off mode power consumption ≤ 33 W

Single package central heat pumps that are space-constrained

SEER 2 ≥ 11.9

HSPF 2 (Region V) ≥ 5.0 

Off mode power consumption ≤ 33 W


 

Three-phase

Energy-using product

Energy performance standard

Single package central heat pumps, other than those that are space-constrained

SEER ≥ 13.4

HSPF (Region V) ≥ 5.3

Single package central heat pumps that are space-constrained

SEER ≥ 13.9

HSPF (Region V) ≥ 5.3

Seasonal energy efficiency ratio (2) – the total cooling of a heat pump in Btu during its normal annual usage period for cooling, divided by the electric power usage in watt-hours during the same period in accordance with 10 C.F.R. Appendix M1/10 C.F.R. Appendix F1.

Heating seasonal performance factor (2) (Region V) – the total heating output of a heat pump during its normal annual usage period for heating, divided by the total electric power input in watt-hours during the same time period in accordance with 10 C.F.R. Appendix M1/10 C.F.R. Appendix F1.

kW = kilowatts
Btu/h = British thermal units per hour

Energy efficiency report requirements

  • name of product
  • brand name
  • model number
  • manufacturer
  • name of the certification body or province whose verification mark will be on the product or its package
  • whether a mathematical model as defined in the Regulations was used to generate any of the information provided below
  • Air-Conditioning, Heating and Refrigeration Institute (AHRI) classification type
  • type
    • single package, other than space-constrained, or
    • space-constrained single package
  • off mode power consumption, in watts
  • phase of electric current
  • cooling capacity in kW (Btu/h)
  • heating capacity at 8.3℃ (47℉) in kW (Btu/h)
  • seasonal energy efficiency ratio (SEER 2)
  • heating seasonal performance factor (HSPF 2) and the region for the factor

Sign in to the Compliance Regulatory Energy Efficiency Database (CREED) to download and submit an energy efficiency report for this product.

This document does not constitute part of the Energy Efficiency Act (Act) or its associated regulations.  This document is an administrative document that is intended to facilitate compliance by the regulated party with the Act and its associated regulations.  This document is not intended to provide legal advice regarding the interpretation of the Act or its associated regulations. If a regulated party has questions about their legal obligations or responsibilities under the Act or its associated regulations, they should seek the advice of legal counsel.